Wood fibre over rafters, mineral wool between

A pitched roof with the insulation at the rafters from the tool's Typical UK roofs group. With the layers below it has a U-value of 0.17 W/m²K, is 294.5 mm thick, and has about 37 kgCO₂e/m² of embodied carbon.

U-value
0.17W/m²K
Overall thickness
294.5mm
Embodied carbon
37kgCO₂e/m²
Fire
Worst class E
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.17
England0.16 W/m²KMisses by 0.01
Wales0.13 W/m²KMisses by 0.04
Scotland0.12 W/m²KMisses by 0.05

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Roof tiles, clay
outside the ventilated cavity: not counted
151–13.7A1
2Ventilated cavity behind cladding
outside the ventilated cavity: not counted
25––0–
3Wood fibre board800.042.00011.0E
4Mineral wool between studs 035
bridged by joists at 600 mm
1500.0353.4445.4A1
5OSB or plywood sheathing120.130.0923.4D-s2,d0
6Plasterboard12.50.210.0603.5A2-s1,d0
Total, with surface resistances294.55.97036.9

U-value worked out to BS EN ISO 6946 from the total resistance. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Free of interstitial condensation No condensation in any month (Heathrow (London), 1 in 10 year). Surface factor 0.96 (needs over 0.72 and at least 0.75).

Rain: Not checked for exposure zone 2 (moderate).

Other typical UK roofs

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.