UK U-value limits for walls, roofs, floors and windows

The highest U-value each element may have under the energy rules in England, Wales and Scotland, in W/m²K. Lower is better insulated. These are the figures the Wall Build-up Visualiser checks against.

Check a build-up against these limitsU-values of common build-ups

England

ElementNew homesExtensions to homesUpgraded elements in homesOther new buildings
External walls0.260.180.300.26
Pitched roofs0.160.150.160.16
Flat roofs0.160.150.160.18
Floors0.180.180.250.18
Windows and glazed walls1.601.401.401.60
Rooflights2.202.202.202.20

From England, Approved Document L 2021; England, Approved Document L 2021, Volume 2. New homes in England are limiting values: to pass the whole-house target a new home usually needs about 0.18 for walls, 0.11 for roofs and 0.13 for floors. "See note" means the tool has no figure loaded for that case: check the current document.

Wales

ElementNew homesExtensions to homesUpgraded elements in homesOther new buildings
External walls0.180.18see notesee note
Pitched roofs0.130.13see notesee note
Flat roofs0.130.13see notesee note
Floors0.150.15see notesee note
Windows and glazed walls1.401.40see notesee note
Rooflights2.202.20see notesee note

From Wales, Approved Document L 2022. Flats may use 0.21 for walls. "See note" means the tool has no figure loaded for that case: check the current document.

Scotland

ElementNew homesExtensions to homesUpgraded elements in homesOther new buildings
External walls0.17see notesee notesee note
Pitched roofs0.12see notesee notesee note
Flat roofs0.12see notesee notesee note
Floors0.15see notesee notesee note
Windows and glazed walls1.40see notesee notesee note
Rooflights1.40see notesee notesee note

From Scotland, Technical Handbook Section 6, 2023 standards. New homes are the maximum area-weighted average. "See note" means the tool has no figure loaded for that case: check the current document.

Regulations change. Always check the current edition of the Approved Document or Technical Handbook for your project, and whether a whole-building calculation sets a tighter target.

Figures come from the Wall Build-up Visualiser's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.