29 Rainscreens

A pitched roof with the insulation at the rafters from the tool's Metal roofs group. With the layers below it has a U-value of 0.18 W/m²K, is 216 mm thick, and has about 109 kgCO₂e/m² of embodied carbon.

U-value
0.18W/m²K
Overall thickness
216mm
Embodied carbon
109kgCO₂e/m²
Fire
Worst class E
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.18
England0.16 W/m²KMisses by 0.02
Wales0.13 W/m²KMisses by 0.05
Scotland0.12 W/m²KMisses by 0.06

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Aluminium rainscreen panel
outside the ventilated cavity: not counted
3160–54.0A1
2Ventilated cavity behind cladding
outside the ventilated cavity: not counted
60––0–
3Single-ply membrane20.20.0108.1E
4PIR board1500.0226.81816.7E
5Profiled steel structural deck1500.00021.7A1
Total, with surface resistances2167.028108.8

U-value worked out to BS EN ISO 6946 from the total resistance, plus 0.040 W/m²K of corrections for fixings, gaps or brackets. Carbon is stages A1 to A3 for the layers, including 8.3 kgCO₂e/m² for steel rails or purlins.

Moisture and rain

Traces only Under 10 g/m² at most, which the tool treats as negligible. Surface factor 0.95 (needs over 0.72 and at least 0.75).

Rain: Not checked for exposure zone 2 (moderate).

Other metal roofs

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.