20 Stone cladding

An external wall from the tool's Masonry walls group. With the layers below it has a U-value of 0.25 W/m²K, is 457.5 mm thick, and has about 110 kgCO₂e/m² of embodied carbon.

U-value
0.25W/m²K
Overall thickness
457.5mm
Embodied carbon
110kgCO₂e/m²
Fire
A2 or better
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.25
England0.26 W/m²KMeets it
Wales0.18 W/m²KMisses by 0.07
Scotland0.17 W/m²KMisses by 0.08

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target, about 0.18 for walls. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Limestone cladding panel
outside the ventilated cavity: not counted
401.7–8.6A1
2Ventilated cavity behind cladding
outside the ventilated cavity: not counted
40––0–
3Mineral wool rainscreen slab1500.0354.28611.5A1
4Reinforced concrete2002.30.08786.4A1
5Unventilated cavity or dab gap15–0.1710–
6Plasterboard12.50.210.0603.5A2-s1,d0
Total, with surface resistances457.54.863110.1

U-value worked out to BS EN ISO 6946 from the total resistance, plus 0.040 W/m²K of corrections for fixings, gaps or brackets. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Free of interstitial condensation No condensation in any month (Heathrow (London), 1 in 10 year). Surface factor 0.94 (needs over 0.71 and at least 0.75).

Rain: Zone 2 of max 4 for exposure zone 2 (moderate).

Other masonry walls

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.