18 Masonry cavity walls, brick

An external wall from the tool's Masonry walls group. With the layers below it has a U-value of 0.18 W/m²K, is 368 mm thick, and has about 96 kgCO₂e/m² of embodied carbon.

U-value
0.18W/m²K
Overall thickness
368mm
Embodied carbon
96kgCO₂e/m²
Fire
Worst class E
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.18
England0.26 W/m²KMeets it
Wales0.18 W/m²KMeets it
Scotland0.17 W/m²KMisses by 0.01

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target, about 0.18 for walls. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Brick, outer leaf102.50.770.13341.5A1
2Unventilated cavity, foil-faced one side50–0.4450–
3PIR board1000.0224.54511.1E
4Brick, inner leaf or protected102.50.560.18341.5A1
5Plaster, dense130.570.0232.0A1
Total, with surface resistances3685.49996.1

U-value worked out to BS EN ISO 6946 from the total resistance. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Traces only Under 10 g/m² at most, which the tool treats as negligible. Surface factor 0.95 (needs over 0.71 and at least 0.75).

Rain: Zone 2 of max 3 for exposure zone 2 (moderate).

Other masonry walls

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.