19 Masonry cavity walls, block

An external wall from the tool's Masonry walls group. With the layers below it has a U-value of 0.18 W/m²K, is 378 mm thick, and has about 51 kgCO₂e/m² of embodied carbon.

U-value
0.18W/m²K
Overall thickness
378mm
Embodied carbon
51kgCO₂e/m²
Fire
A2 or better
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.18
England0.26 W/m²KMeets it
Wales0.18 W/m²KMeets it
Scotland0.17 W/m²KMisses by 0.01

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target, about 0.18 for walls. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Sand-cement render1510.0155.7A1
2Dense concrete block1001.130.08820.0A1
3Mineral wool cavity batt 0321500.0324.6886.1A1
4Aircrete block, standard
bridged by mortar joints
1000.150.50316.8A1
5Plaster, dense130.570.0232.0A1
Total, with surface resistances3785.54850.6

U-value worked out to BS EN ISO 6946 from the total resistance. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Fails: condensate builds up year on year Up to 1002 g/m² at between dense concrete block and mineral wool cavity batt 032 (part 1 of 19), with some left after 12 months. Surface factor 0.95 (needs over 0.71 and at least 0.75).

Rain: Zone 2 of max 4 for exposure zone 2 (moderate).

Other masonry walls

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.