02 Profiled metal cladding

An external wall from the tool's Metal walls group. With the layers below it has a U-value of 0.24 W/m²K, is 181.2 mm thick, and has about 38 kgCO₂e/m² of embodied carbon.

U-value
0.24W/m²K
Overall thickness
181.2mm
Embodied carbon
38kgCO₂e/m²
Fire
A2 or better
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.24
England0.26 W/m²KMeets it
Wales0.18 W/m²KMisses by 0.06
Scotland0.17 W/m²KMisses by 0.07

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target, about 0.18 for walls. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Profiled steel sheet or panel facing0.7500.00015.2A1
2Mineral wool quilt for built-up metal systems1800.044.5003.4A1
3Steel liner sheet or tray0.5500.00010.8A1
Total, with surface resistances181.24.67037.7

U-value worked out to BS EN ISO 6946 from the total resistance, plus 0.030 W/m²K of corrections for fixings, gaps or brackets. Carbon is stages A1 to A3 for the layers, including 8.3 kgCO₂e/m² for steel rails or purlins.

Moisture and rain

Condenses in winter, dries by summer Up to 20 g/m² at between profiled steel sheet or panel facing and mineral wool quilt for built-up metal systems (part 1 of 18), all of it drying out over the year. Surface factor 0.94 (needs over 0.71 and at least 0.75).

Rain: Face-sealed for exposure zone 2 (moderate).

Other metal walls

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.