01 Sheet metal

An external wall from the tool's Metal walls group. With the layers below it has a U-value of 0.19 W/m²K, is 386.3 mm thick, and has about 67 kgCO₂e/m² of embodied carbon.

U-value
0.19W/m²K
Overall thickness
386.3mm
Embodied carbon
67kgCO₂e/m²
Fire
Worst class D
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.19
England0.26 W/m²KMeets it
Wales0.18 W/m²KMisses by 0.01
Scotland0.17 W/m²KMisses by 0.02

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target, about 0.18 for walls. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Zinc sheet, standing seam
outside the ventilated cavity: not counted
0.8110–17.7A1
2OSB or plywood sheathing
outside the ventilated cavity: not counted
180.13–5.1D-s2,d0
3Ventilated cavity behind cladding
outside the ventilated cavity: not counted
40––0–
4Mineral wool rainscreen slab1600.0354.57112.3A1
5Dense concrete block1401.130.12428.0A1
6Unventilated cavity or dab gap15–0.1710–
7Plasterboard12.50.210.0603.5A2-s1,d0
Total, with surface resistances386.35.18666.5

U-value worked out to BS EN ISO 6946 from the total resistance. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Free of interstitial condensation No condensation in any month (Heathrow (London), 1 in 10 year). Surface factor 0.95 (needs over 0.71 and at least 0.75).

Rain: 15 mm drained cavity for exposure zone 2 (moderate).

Other metal walls

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.