Uninsulated concrete slab

A solid ground floor from the tool's Typical UK floors group. With the layers below it has a U-value of 0.56 W/m²K, is 200 mm thick, and has about 86 kgCO₂e/m² of embodied carbon.

U-value
0.56W/m²K
Overall thickness
200mm
Embodied carbon
86kgCO₂e/m²
Fire
A2 or better
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.56
England0.18 W/m²KMisses by 0.38
Wales0.15 W/m²KMisses by 0.41
Scotland0.15 W/m²KMisses by 0.41

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Reinforced concrete1502.30.06564.8A1
2Sand-cement screed501.150.04321.0A1
Total, with surface resistances2000.31985.8

U-value worked out to BS EN ISO 6946 from the total resistance. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Not checked Ground-bearing floors need 2 m of soil in the model and ground temperatures (BS 5250 13.2.2.3), which this tool does not do.

Rain: Not checked for exposure zone 2 (moderate).

Other typical UK floors

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.