Cavity wall, full-fill mineral wool

An external wall from the tool's Typical UK walls group. With the layers below it has a U-value of 0.17 W/m²K, is 380 mm thick, and has about 68 kgCO₂e/m² of embodied carbon.

U-value
0.17W/m²K
Overall thickness
380mm
Embodied carbon
68kgCO₂e/m²
Fire
A2 or better
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.17
England0.26 W/m²KMeets it
Wales0.18 W/m²KMeets it
Scotland0.17 W/m²KMeets it

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target, about 0.18 for walls. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Brick, outer leaf102.50.770.13341.5A1
2Mineral wool cavity batt 0321500.0324.6886.1A1
3Aircrete block, standard
bridged by mortar joints
1000.150.50316.8A1
4Unventilated cavity or dab gap15–0.1710–
5Plasterboard12.50.210.0603.5A2-s1,d0
Total, with surface resistances3805.78667.9

U-value worked out to BS EN ISO 6946 from the total resistance. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Traces only Only on the back of the masonry outer leaf, which is wet from rain anyway, or under 10 g/m² in total. Surface factor 0.96 (needs over 0.71 and at least 0.75).

Rain: Zone 2 of max 4 for exposure zone 2 (moderate).

Other typical UK walls

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.