24 Cladding the timber frame

An external wall from the tool's Timber walls group. With the layers below it has a U-value of 0.17 W/m²K, is 259.5 mm thick, and has about 21 kgCO₂e/m² of embodied carbon.

U-value
0.17W/m²K
Overall thickness
259.5mm
Embodied carbon
21kgCO₂e/m²
Fire
Worst class E
Open this build-up in the toolChange layers, check fire and condensation for your own project, and export a PDF.

Against the Building Regulations

New home inU-value limitThis build-up, 0.17
England0.26 W/m²KMeets it
Wales0.18 W/m²KMeets it
Scotland0.17 W/m²KMeets it

These are the limits for a single element in a new home. In England a new home usually needs better figures to pass the whole-house target, about 0.18 for walls. All UK U-value limits.

Section, drawn to scale

Layers, outside to inside

#Layermmλ, W/mKR, m²K/WkgCO₂e/m²Fire class
1Timber cladding
outside the ventilated cavity: not counted
200.13–2.5D-s2,d0
2Ventilated cavity behind cladding
outside the ventilated cavity: not counted
25––0–
3OSB or plywood sheathing120.130.0923.4D-s2,d0
4Mineral wool between studs 035
bridged by timber studs
1400.0352.8435.9A1
5PIR board500.0222.2735.6E
6Plasterboard12.50.210.0603.5A2-s1,d0
Total, with surface resistances259.55.75720.9

U-value worked out to BS EN ISO 6946 from the total resistance. Carbon is stages A1 to A3 for the layers.

Moisture and rain

Free of interstitial condensation No condensation in any month (Heathrow (London), 1 in 10 year). Surface factor 0.96 (needs over 0.71 and at least 0.75).

Rain: Rainscreen for exposure zone 2 (moderate).

Other timber walls

Figures come from the Build-up Atlas's own calculation, with generalised values for typical products, for an England new home with default settings. They are indicative, for design and teaching: check the manufacturer's declared values and the current regulations for your project. Rules and standards last checked 21 October 2026.